Request a copy of the presentation by simply filling out the form below:
[contact-form-7 id=”830″ title=”Merits and Plant Specific Experience with Pilot-Scale SCR Catalyst Testing”]
ICT’s presentation “Maximizing the Value from Catalyst Sampling and Testing” from Reinhold NOx-Combustion-CCR/PCUG Conference in February 2019 is now online. If you missed the conference, don’t worry… you can download it below.
Request a copy of the presentation by simply filling out the form below:
[contact-form-7 id=”818″ title=”Contact form 1_copy”]

For various reasons, some layers will deactivate at irregular intervals. That’s why catalyst should to be checked regularly to ensure it is run to the end of usable life, rather replaced simply because the manufacturer says it should be.
At Innovative Combustion Technologies we think that’s a bit like having a fox in the henhouse — taking catalyst replacement advice from the company that’s selling you the catalyst. It doesn’t make a lot of sense. As the only independent pilot-scale SCR catalyst testing facility in the U.S., ICT provides power plants unbiased data, independent of the original equipment manufacturer and regeneration companies. At the end of the day, that means potentially saving millions in operating costs with the confidence your catalyst meets the required operational specifications.
Conventional wisdom would have required Plant A to replace four separate catalyst layers over a 3-year period. However, catalyst testing proved that NOx reduction targets could be achieved with only three replacements over the same period. Eliminating a single catalyst replacement, yielded a net savings of $1.4M over the 3-year period with the investment of $48k/year in a catalyst testing program.
ROI: 970%


Plant B operates their SCR system on a seasonal basis, which means the catalyst is exposed to less flue gas than it would be under year-round operation. In addition to the limited flue gas exposure, ICT’s catalyst testing revealed that deactivation rates for all three layers were slower than the standard trend. The findings were able to save Plant B $2M, over a 4-year period, with the implementation a $48k/year catalyst testing program. ICT was able to determine the absolute lifetime of the catalyst, which differed from what the manufacturer suggested, allowing Plant B to run the catalyst to the end of usable life with the confidence that they’re not going to risk a compliance issue.
ROI: 1,000% over a 4 year period


In 2017, Plant C switched to a more cost-effective type of coal. But the switch had unintended consequences and reduced the DeNOx activity of individual layers by 40-70%.
In this case, ICT’s testing revealed the catalyst was decreasing in performance much more rapidly than expected following the fuel switch. Because they were regularly testing their catalyst, Plant C was able to move up their next catalyst replacement to prevent a compliance issue. They were also then able to change how they operated the plant to mitigate the arsenic poisoning as much as possible.

ICT to host open house: Guests can learn about new pilot-scale catalyst test facility Nov. 14th-15th, 2018.
Open House Schedule
Wednesday 11/14: 8 a.m. -5 p.m.
Thursday 11/15: 8 a.m. – 5p.m.
For more information, contact: Elizabeth ~ epatton@innovativecombustion.com
Innovative Combustion Technologies, Inc. (ICT) is proud to announce an agreement has been reached with Southern Research to manage and operate its bench-scale SCR catalyst testing facility, effective November 1, 2016. With this agreement, ICT adds the capability to provide catalyst activity testing to its existing SCR tuning and performance field testing capabilities. ICT will continue to operate the facility as an objective third-party to meet the SCR catalyst testing needs of the electric power industry.
To ensure the integrity and validity of the testing and performance data reported by the facility, ICT will be a principal participant in “round-robin” catalyst testing program administered by the Electric Power Research Institute (EPRI) that provides comparisons in results achieved by multiple bench-scale facilities. ICT will also be providing data stemming facility to EPRI on a voluntary and site anonymous basis to build databases of correlation data when permitted by customers of the facility. This will benefit EPRI’s members and the electric power industry as a whole to evaluate SCR best practices, identifying opportunities to lower O&M expenses, determining factors that impact catalyst life or performance, performance enhancements and compiling long-term catalyst performance data to support sound catalyst management decisions.
SCR System Management
Since SCR catalysts degrade in performance with time, especially for solid fuels that can contain various poisons, a proper catalyst management program must account for the catalyst degradation trend as well as the SCR System’s overall performance. SCR owners and operators must have detailed knowledge of both of these variables in order to make accurate decisions regarding catalyst replacement cycles and outage schedules, while also minimizing your Capital and Operational Budget.
ICT has a 20+ year history of providing emissions and boiler testing services to its clients worldwide. In 2011, ICT formed its Environmental Services group in order to provide stack and pollution control equipment performance testing services to its clients to augment the boiler and pulverizer testing services already offered. ICT has provided the field testing services required to document SCR System performance and to tune the system to maximize performance, minimize operating costs, and meet all emissions guarantees and regulations. By pairing its testing services with the Catalyst Testing Facility, ICT now has the capability to provide the full range of services required to maintain optimal SCR System performance and SCR System management practices and procedures.
Questions You Should Ask About Your SCR
Operational Budget?
If you are unsure about the answers to any or all of these questions, ICT has the equipment, experience, and personnel to troubleshoot any issues associated with SCR Systems.
Marcus Harton
Environmental and Research Engineering Manager Innovative Combustion Technologies, inc. 205-453-0236 mharton@innovativecombustion.com
Richard Storm
President
Innovative Combustion Technologies, inc. 205-453-0236 richardstorm@innovativecombustion.com
Innovative Combustion Technologies, Inc.
10 Commerce Drive Pelham, AL 35124 www.innovativecombustion.com
Common Analyses used for SCR Catalysts Include:
About the SCR Facility Design:
The Bench-Scale Test Facility is uniquely designed to provide high sample throughput with maximum control and data accuracy. An 800,000 Btu/hr natural gas furnace produces approximately 200 scfm of flue gas, which is cooled and reheated to control moisture content to the desired level. Supplemental electric heat provides fine control, with typical testing temperatures up to 750°F and higher, if required. Ammonia is injected into the furnace to provide the desired level of NOx. Catalyst samples are tested in (3) test chambers, while (4) downstream aging chamber allow multiple catalysts to be aged while testing is being conducted. This maximizes sample throughput and helps to minimize costs. Bottled liquefied SO2 and SO2 conversion reactor provide the required levels of flue gas SO2 and SO3. If desired, the facility can be operated with (2) catalysts in series, fully simulating a full-scale two-layer SCR.
Capabilities Associated with Bench-Scale Testing Include:
• Determination of SCR catalyst de-NOx activity
• Determination of SO2-to-SO3 conversion rates
• Determination of mercury oxidation rate to be added in the near future
• Physical inspection and dimensional measurements to confirm geometric design and evaluate fouling and structural integrity
• Data compilation and storage to enable historical trends
• Storage of catalyst samples
• Determination of catalyst chemical properties
Innovative Combustion Technologies, Inc.
Innovative Combustion Technologies (ICT) is excited to announce that we are the new North Ameri- can sales agent for Loesche Energy Systems, Ltd. (LES) of the United Kingdom for dynamic classifiers, pulver- izers and technical services associated with size reduction of solid fuels for the power industry.
Loesche GmbH was founded in 1906 in Berlin, Germany. This family-owned company has a 100+ year history of designing and supplying grinding and classifying equipment to the power and cement industry. With their leading technology and +850 dedicated employees, manufacturing plants, 18 operating units and agents they offer the best available technology along with novel solutions to industry.
Loesche Energy Systems, a subsidiary of Loesche GmbH, was launched 10 years ago as a Centre of Excellence within the group for coal mill application to power generation utilities worldwide. Loesche has designed, built and delivered over 420 dynamic classifiers to utilities meeting and often exceeding expected performance guarantees. The reference list includes dynamic classifier retrofits to manufactures of vertical spindle, ball tube mills and ball in race pulverizers in North America, Europe, Asia and Africa.
The collaboration between LES and ICT combines two companies that are committed to providing their customers with the best solutions for attaining optimum combustion. ICT’s core services and products have been focused on improving combustion, boiler performance and emissions since its inception in 1993. It is ICT’s opinion that Loesche’s dynamic classifiers and other equipment are “best in class” and will enhance ICT’s ability to better serve the needs of our customers and improve in our core services.
Not only are LES’ dynamic classifiers designed to improve combustion, they are also an essential com- ponent for strategies that are aimed to:
Operators of coal fired plants are acutely aware of the effect pulverizer performance has on the boiler system; raw coal throughput, efficiency, reliability and emissions are all impacted by poor pulverizer perfor- mance. Improving fuel distribution and fineness are among the most important factors in optimizing com- bustion. Loesche Dynamic Classifiers can offer the solution for optimizing combustion on a unit; as they have been proven to improve fineness, increase pulverizer throughput, improve fuel distribution, minimize pulverizer grinding element wear, reduce pulverizer pressure drop, and can lead to a ±10% reduction in NOxemissions. These benefits can be realized on all PC units, regardless of the type of coal fired.
For more information, please contact:
Oz Imaghodor
Coal Pulverizer Systems Engineer Innovative Combustion Technologies, inc. 205-453-0236 oz.imaghodor@innovativecombustion.com
Richard Storm
President
Innovative Combustion Technologies, inc. 205-453-0236 richardstorm@innovativecombustion.com
10 Commerce Drive Pelham, AL 35124 www.innovativecombustion.com
Objectives and Benefits of Dynamic Classifiers:
moisture coal which allows higher mill outlet temperature when mill outlet temperature is low.
Pulverized Coal Outlets
Grit Cone
Raw Coal Inlet Bearing Cartridge
Classifier Housing
Static Guide Vanes Rotor Cage
reduces chances of NH3 and ABS fouling
heater and SCR
pulverizer out of service due to increased
capacity.
optimization for fineness when coal quality
changes.
Mills, and all vertical spindle mills (Raymond Bowl mill, MPS, MBF, E and EL mills).
• Over 420 retrofits completed globally 2002
LES Dynamic Classifier Retrofits 2001-2015
Mill Inerting and
Pulverizer/Mill Explosion Mitigation
Richard P. Stormrichardstorm@innovativecombustion.com (205) 453-0236
2013 Annual Meeting | WWW.PRBCOALS.COM
Coal Mills are the Heart of a Coal Fired Plant
Maximum capacity, reliability and performance of your operation rely on the critical roles that your coal mills perform:
There are risks…..
Mill inerting is regarded as the principal approach or engineering control to prevent mill fires & explosions
Steam, CO2 and N2 Inerting Systems
Water Fogging/Deluge
All of these systems can be effective in reducing the risk of mill fire/explosion or limiting damage (explosion suppression systems). Each has strengths and weaknesses.
Some plants have operated safely with and without these systems.
All of these systems can be effective in reducing the risk of mill fire/explosion or limiting damage (explosion suppression systems). Each has strengths and weaknesses.
• Some plants operate with and without these systems. Coal characteristics profoundly influence risk, PRB coal is one of the most difficult coals with respect to mill fires/explosions with greater magnitude explosions.
The Kst (Explosibility Constant or Deflagration Index) value for sub-bituminous coals are higher than for bituminous coals. Sub-bituminous coals have a higher rate of pressure rise if an explosion (deflagration) occurs.
|
Type of Coal |
Kst |
|
Sub-Bituminous1 |
200 bar-m/sec |
|
Bituminous1,2,3 |
55-154 bar-m/sec |
|
Lignite3 |
123 bar-m/sec |
1 Options for Biomass Fuels Utilization in Power Plants, 2011, Don Koza 2 NFPA 68 Guide for Venting of Deflagration, 1998
3 Dust Explosions in the Process Industries, 1991, R.K. Eckhoff
Some units without these systems have prevented or managed fire and explosion risks by:
• Feed interruptions caused by wet or frozen coal.
An understanding of what causes mill fires and explosions is required for safe operation and optimal results with any type of system that inhibit mill fires or explosions.
Most utility boiler coal mills do and should operate at primary air to coal ratios of 2:1 or less.
Coal Mill Air to fuel ratios are higher during:
In the example below, which is typical, Mill air flow is held constant at 140,000 Lbs./Hr. at coal flows <78,000 Lbs./Hr. to maintain minimum burner line of 3,500 Fpm.
A common assumption is that at full load coal flows, air to fuel ratio us too low for pre-ignition of coal or below the explosive or combustible range inside the coal mill.
Hot Temperatures always exist inside the coal mill while firing PRB Coal
135° to 145°F
150° to 160°F
500° to 700°F
Typical temperature inside the mill with Coal Moisture of 30% Higher Moisture = Higher temperatures and higher risk of mill fire
Typical temperature inside the mill with Coal Moisture of 3% Less Moisture = Lower Mill Inlet Temperatures
– despite the Higher Outlet Temperature
100,000 LBS/HR Coal X 3% Moisture
= 3,000 Moisture
Typical Temperature of a Pulverizer – Inlet Temperatures will high regardless of pulverizer manufacturer with high moisture coal.
130°F – 140°F
140°F – 160°F
Between 500°F & 700°F
COMMON CAUSE OF MILL FIRES:
COAL SPILLAGE UNDER THE BOWL
Air-to-Fuel Ratio by Design
~1.8:1
Air-to-Fuel Ratio
Very High
500°F – 700°F
Coal feed is interrupted either intentionally or unintentionally during start-up and shutdown of the mill or due to clogging or equipment failure
Because there is no longer a flow of coal – which normally absorbs heat through the evaporation of the coal’s moisture content – the high temperatures typical of the under bowl/under table area migrate upward into the grinding zone
The decreased quantity of coal also means there is an increase in the air-to-fuel ratio
The combination of high temperatures and a
high air-to-fuel ratio causes the coal remaining in the grinding zone to ignite
Typical internal temperature
130°F – 140°F 58°C – 68°C
140°F – 160°F 60°C – 70°C
500°F – 700°F 250°C – 300°C
3) 4)
TYPICAL PROGRESSION OF A MILL FIRE
Mill Fires: Potential Areas
Feeder
Coal piping
Classifier Section
Above the grinding bowl
Under the grinding bowl
Exhauster
COMMON CAUSES OF FIRES, PUFFS & EXPLOSIONS
Smoldering coal from the bunker reaches a point of deflagration (bursts into flames) as it travels through the feeder down to the mill
Raw coal supply is interrupted due to imprecise feeder control and stoppages above and below the feeder
Accumulation and settling in pulverizer components allow coal to dry – such accumulations can spontaneously ignite
Most pulverizer fires and/or puffs are caused by coal spilling into the high temperature area where primary air enters the mill.
Excessive pulverizer airflow provides an abundant source of air for combustion of ignition sources including smoldering coal in the classifier, pulverizer or raw coal in the high temperature under bowl
Raw coal which is allowed to spill over into the under bowl section accumulate and are exposed to temperatures >500̊F
2013 Annual Meeting | WWW.PRBCOALS.COM
Worn or Improper (oversized) Components can allow coal spillage into the high temperature zone below the grinding zone
Smoldering Coal from aboveSmoldering coal from the bunker
– Reachesapointofdeflagrationasit travels through the feeder, and into the mill
Smoldering coal that has no
access to oxygen in the tightly
packed bunker
– Willsuddenlybeexposedtooxygen as it breaks apart in transit
– Thereisalsoadecreaseinparticle size
Common Causes of Mill Fires Accumulation
Accumulations of debris or coalanywhere in the pulverizer will increase the chance of a mill fire
Accumulation and settling in pulverizer components allow coal to dry
Common Causes of Mill Fires Poor Airflow Control
Excessive airflow to the pulverizer
Provides an abundant source of air for combustion of ignition sources including smouldering coal in the classifier, pulverizer or raw coal under the bowl
Sufficient air velocity should be maintained at all loads to prevent the settling of coal from the air stream
MillPro Mill Protection System
A Proactive Mill Protection System for Coal Fired Power Plants
Incorporates
Mill outlet temperature management
Faster cooling with less water.
Mill fogging, internal combustible dust suppression
Fire suppression
Operates continuously while mill is in service2013 Annual Meeting | WWW.PRBCOALS.COM
Hazard Control Technologies (HCT) are experts on chemistries that rapidly reduce the temperature of hot coal, as proven through F-500. MillPro TS-EA builds on this technology to reduce high internal mill temperatures faster.
At the same application density of 0.30 gpm/ft2, the temperature of the MillPro TS-EA drops to 118 ̊F in 10 seconds, 3 times faster than plain water
Rapid Suppression/Extinguishment
• Key to the MillPro System – the MillPro TS-EA– Controls the temperature inside the mill
environment
─ More effective than traditional solutions or water alone
– Unique molecular design
─ allows for specific alignment within a water droplet to
accomplish significantly higher heat reduction
– Once injected into the pulverizer as a fine mist,
cooling begins immediately
─ reducing damage to your equipment and returning
your mill to standard operating conditions within seconds
MillPro vs. Traditional Systems
|
MillPro |
Steam |
Water /Fog |
|
|
Inhibits mill excursions during start-up & shut-down |
|
|
|
|
Inhibits mill excursions due to coal feed interruptions |
|
||
|
Internal fire suppression/extinguishing system |
|
||
|
External fire suppression/combustible dust management |
|
||
|
Rapid cooling of mill internals leading to decreased maintenance intervals |
|
||
|
Helps manage mill outlet temperature excursions before they evolve into fires |
|
||
|
Operates while the mill is in service |
|
||
|
Low water requirements |
|
||
|
Uniform cooling of mill internals |
|
||
|
Functions as mill internal wash down |
|
|
|
|
Can be integrated to protect the entire fuel burning system |
|
||
|
In case a fire does occur, accelerated fire suppression and heat removal results in minimizing damage to mill internals |
|